EbrilsmartP

LABORATORY TESTS

LEAKAGE TEST EN 1779.B6
This test calculates the annual loss of coolant: the recommended threshold is 1g/year; we measured a loss of <50 mg/year.
BURST TEST EN 378-2
This test measures the pressure resistance of the fittings. After the test- ing, the fittings remained intact at a maximum pressure of 200bar.

INSTALLATION

Insert the tube, previously cut and deburred, into the nut and then insert the sleeve.
Tighten the nut to the joint by hand.
Mark the starting point and make a complete turn and a half with the aid of a common wrench.
Mark the starting point and make a complete turn and a half with the aid of a common wrench.

EbrilSmart technical specifications

  • Operating temperature: from -45°C to +150°C
  • Maximum operating pressure: 45bar
  • Suitable for all coolants R407C, R410A, R32
  • Triple metallic seal
  • Suitable for traditional 45° flare fittings
  • Torque wrench not required for installation
  • To be used exclusively on R220 annealed copper pipes and OH111 aluminium tubes

EbrilSmart certifications

  • In compliance with the European Directives PED, RoHS and REACH
  • Superior performances in comparison to the traditional 45°flare fittings

Applications

  • Air conditioning systems
  • For copper and aluminium pipes

Specifications

  • Universal self flare fittings